    • ApplicationsHeating and cooling, plumbing and waste water, especially in tight spaces in mechanical rooms where parallel pumping is needed with or without optional standby pump
    • DescriptionThe Armstrong 8200 ARMPak pumping packages are specifically designed to meet the requirements of chilled water and heating water systems in commercial buildings. They are available in duplex and triplex configurations, with fixed or variable speed control. Suitable for space constrained installation, parallel pumping and optional stand-by pump
    • Configuration4280V or 4200V pumps, Flo-Trex valves, optional IPS controls and variable frequency drive(s) with bypasses, NEMA 1 control panel (including gauges and interconnecting piping), headers, valves, and fittings
    • Size3”, 4” and 6” header sizes
    • ApplicationsEnergy optimization of HVAC chilled-water plants with partial or all variable speed equipment and an existing building automation system (BAS) or central plant controller.
    • DescriptionThe Armstrong OPTI-VISOR interfaces seamlessly with any existing building automation to maximize overall plant efficiency – without replacing or reconfiguring existing componentry. The OPTI-VISOR harmonizes the interplay of existing componentry through leading-edge control algorithms for maximum plant performance.
    • ConfigurationIntegrates with all brands of chillers, pumps, and building automation systems
    • Performance rangeNo limitations in plant size and cooling capacity
    • Power RangeNo limitations in plant size and cooling capacity
    • ApplicationsCommercial or industrial closed-loop systems, including HVAC chilled-water systems, boiler systems, cooling tower systems, or process water loops.
    • DescriptionThe Armstrong Intelligent Fluid Management System (iFMS) integrates superior pump- and control technology into a single pumping solution yielding both compact and carefree installation as well as superior energy performance. iFMS is ideally suited for partial or all variable speed chilled-water plant applications (variable primary flow, variable secondary flow, variable condenser water flow). In combination with Parallel Sensorless control iFMS saves 30% or more in energy over any other parallel pumping configuration available today.
    • ConfigurationUp to 4 pumps in one unit. Catalogue-based pre-engineered solutions or designed to customer specification. Integrated control system (IPS 4000, IPC 11550) or connecting to chiller plant/BMS control. Optional single point power panel
    • ApplicationsAir-cooled or water-cooled chilled water system automation for data centers
    • DescriptionThe Armstrong Design Envelope EVERCOOL system is an integrated automation and optimization solution for data center chiller plants. Designed to meet the Uptime Institute requirements for all Tiers of data centers, this mission critical platform has also been standardized for speed to market and quick deployment.
    • ConfigurationIntegrates with all brands of chillers, pumps, and automation systems. Installs directly with chiller plant equipment. If preferred, the EVERCOOL connects with any data center information management (DCIM) system or central building automation system (BAS).
    • Performance rangeStandardized solution controls up to six chillers, six cooling towers, six chilled water pumps, six condenser water pumps (when applicable) and redundant sensors and valves.
      Project-specific requirements may include free-cooling, water-side economizer, chilled water storage tanks, etc.
      No limitations in plant size and cooling capacity.
    • ApplicationsCommercial and industrial chilled-water cooling systems
    • DescriptionThe Armstrong Chilled-Water Integrated Plant Package combines all the equipment needed to deliver chilled water to medium to large size buildings at superior energy efficiency. The factory-assembled plant includes pumps, integrated controls, water-cooled chillers and the requisite instrumentation, valves and sensors. IPP complies with all ASHRAE 189.1 requirements and exceeds ASHRAE 90.1.
    • ConfigurationVariable primary with variable condenser flow. Catalogue-based pre-engineered solutions or designed to customer specification. BMS communications protocol available
    • ApplicationsHVAC-system pumping and control; general purpose pumping; industrial/process pumping and control (water or glycol based)
    • DescriptionPipe-mounted UL 778 pumping unit with integrated intelligent controls for space-saving installation and superior energy performance. Saves up to 75% in energy over comparable traditional constant speed or variable frequency operated pump installations. Remote services through internet to enhance reliability and sustain optimal performance over life of pumps.
    • Materials
      • Ductile iron e-coated casing
      • Stainless steel impeller
      • Sintered silicon carbide mechanical seal
    • ConfigurationOn-board Intelligent Variable Speed controls with Sensorless control. Split-coupling design and outside balanced or inside single spring mechanical seal. Controls enclosure UL type 12 or UL type 4X for outdoor applications. 0.33-50hp range standard with DEPM motors that reduce losses by more than 20% over NEMA Premium efficiency. Network capable for remote performance management services.
    • Performance range25 to 25,000 USgpm (1.5 to 1500 L/s) flow; 10 to 300 ft (3 to 90 m) head (composite curves available)
    • Temperature300oF (150oC)
    • Power Range0.33 hp to 1250 hp (0.25 kW to 900 kW)
    • Size1″ to 20″ (25 mm to 500 mm)
    • ApplicationsHVAC-system pumping and control, general purpose pumping (water or glycol based)
    • DescriptionA retrofit of an existing constant speed Armstrong Vertical In-line to a Armstrong Design Envelope Vertical In-line pump utilizing the existing casing and replacing all other components.

      Pipe-mounted with integrated intelligent controls for continued space savings and superior energy performance.  Saves up to 70% in energy compared to traditional constant speed pump installations.

    • Materials
      • Cast-iron or ductile iron casing
      • Bronze impeller
      • Sintered silicon carbide mechanical seal
    • ConfigurationOn-board intelligent variable speed controls with Sensorless control.  Split coupling and outside balanced or inside single spring mechanical seal.  Controls enclosure UL type 12 or UL type 4X for outdoor applications.
    • Performance range25- 25,000 US gpm (1.5 to 1500 L/S) flow, 10 – 300 ft (3 to 90m) head  (composite curves available)
    • TemperatureUp to 300oF (150oC)
    • Power Range1 hp to 1250 hp (0.75 kW to 900 kW)
    • Size1.5” to 15” (40 mm to 400 mm)
    • ApplicationsHVAC-system pumping and control; general purpose pumping; industrial/ process pumping and control (water or glycol based)
    • DescriptionBase mounted end-suction horizontal pumping unit with integrated intelligent controls for easier installation and superior energy performance. Saves up to 75% in energy over comparable traditional constant speed or variable frequency operated pump installations. Units up to 10hp (7.5kW) include integral vibration isolators.
    • Materials
      • Cast-iron or ductile iron casing / ductile iron e-coated casing on units 1-10hp
      • Bronze or stainless steel impeller on units 1-10hp
      • Sintered silicon carbide mechanical seal
    • ConfigurationOn-board Intelligent Variable Speed controls with Sensorless control. Controls enclosure UL Type 12 (IP55) indoor applications. 1-10hp (0.75-7.5 kW) range standard with Design Envelope permanent magnet (DEPM) motors that reduce losses by more than 20% over NEMA Premium efficiency. Network capable for remote performance management services.
    • Performance range25 to 1000 USgpm (1.5 to 63 L/s) flow; 10 to 160 ft (3 to 48 m) head (composite curves available)
    • Temperature250oF (121oC)
    • Power Range1 hp to 10 hp (0.75 kW to 7.5 kW)
    • Size1.25″ to 6″ discharge (32 mm to 150 mm)